Power is always needed. Critical systems must always be online, whether they're for the safety of humans or animals or production processes that must keep running. After a power cut, damage and losses can occur in a matter of minutes. Valtra generators use the entire range of AGCO POWER engines from Linnavuori with six models from 60 kVA to 250 kVA.
An emergency power supply must work whenever it's needed. That's why Valtra generators are manufactured with high-quality components and solutions that have proven their worth many times over the years. You have the highest demands for quality. And so do we. For decades, we've been involved in developing industrial products and meeting the requirements of our customers. We know what's expected of us. Our products have been tested to meet the requirements of the cold Arctic as well as the heat of Africa. All engines are checked carefully before assembly and all functions of our generators are tested before being shipped to the customer.
Our power generators are available as open equipment or enclosed by acoustic insulation for outdoor use. Generators for outdoor use are ready for operation with pre-assembled exhaust pipes and robust support structures.
All generators are designed for stationary use, but thanks to their compact dimensions are also easy to handle and transport.
All Valtra generators are available with the same operating modes and functions. Customers can choose between different configurations from manual operation to automatic emergency power supply.
Manually operated generators are designed especially for use in areas where mains power is not available. At remote sites, a diesel generator is often more economical than routing a new power line to the location.
The automatic mechanism starts the engine within seconds of a power cut and switches it off again automatically when the mains power returns. For demanding locations, the power generators can be equipped with automatic operation with synchronisation. With synchronisation, the generator can supply power in parallel to the power supply. This allows a seamless change-over in the event of a power cut, uninterrupted test runs and coverage of peak loads if some loads exceed the amperage of the main fuse.
Model | VG60 | VG90 | VG110 | VG150 | VG205 | VG250 |
---|---|---|---|---|---|---|
Power Prime (PRP) kVA / kW | 60 / 48 | 90 / 72 | 110 / 88 | 150 / 120 | 205 / 164 | 250 / 200 |
Power Standby (LTP) kVA / kW | 66 / 53 | 99 / 79 | 121 / 97 | 165 / 132 | 225 / 180 | 275 / 220 |
Engine model (AGCO POWER) | 33 DTG | 49 DTG | 49 DTAG | 74 DTG | 74 DTAG | 84 WIG |
Cylinder qty | 3 | 4 | 4 | 6 | 6 | 6 |
Rev. speed, rpm | 1.500 | 1.500 | 1.500 | 1.500 | 1.500 | 1.500 |
Generator | ECP322M4B | ECP342S4A | ECP341L4A | ECP342L4A | ECO383S4A | ECO381L4A |
Power factor, cos φ | 0,8 ind. | 0,8 ind. | 0,8 ind. | 0,8 ind. | 0,8 ind. | 0,8 ind. |
Electric system voltage, V | 12 VDC | 12 VDC | 12 VDC | 12 VDC | 12 VDC | 12 VDC |
Generator IP protection rating | IP23 | IP23 | IP23 | IP23 | IP23 | IP23 |
Aggregate nominal voltage, V | 400 / 230 | 400 / 230 | 400 / 230, | 400 / 230 | 400 / 230 | 400 / 230 |
Combustion air, m³/min | 5 | 7,5 | 10 | 12,6 | 17 | 15,5 |
Cooling air, m³/min | 110 | 145 | 174 | 216 | 234 | 300 |
Opening f. d. cooling air m² | 0,36 | 0,48 | 0,55 | 0,64 | 0,8 | 1,0 |
Aggregate nominal current, A (PRP) | 87 | 130 | 159 | 218 | 296 | 361 |
Rated current of the electr. Systems A | 125 | 160 | 250 | 250 | 400 | 400 |
Main Fuses, A | 100 | 160 | 250 | 250 | 400 | 630 |
Short circuit current, A, 10 s | > 261 | > 390 | > 477 | > 654 | > 888 | > 1.083 |
Fuel tank capacity (l) | 200 / 200 | 200 / 300 | 350 / 300 | 350 / 300 | 350 / 300 | 350 / 350 |
Working hours with full tank at 100% power, (open / weather protected) | 13 / 13 | 8,5 / 13 | 13 / 11,5 | 10 / 8,5 | 7 / 6 | 7 / 7 |
Fuel consumption @ 100% PRP (l/h) | 14,7 | 23 | 26 | 34 | 48,5 | 49 |
Noise level, weather protected, dB (Lp (7 m) / Lw) | 66 / 90,9 | 71,4 / 96,3 | 72,7 / 97,6 | 71,1 / 96 | 74,2 / 99,1 | 73,3 / 98,2 |
Length, open / weather protected (mm) | 2.180 / 2.310 | 2.250 / 2.920 | 2.650 / 2.920 | 2.750 / 2.920 | 2.850 / 2.920 | 3.220 / 4.210 |
Width, open / weather protected (mm) | 660 / 1.120 | 660 / 1.150 | 990 / 1.150 | 850 / 1.150 | 990 / 1.150 | 1.100 / 1.365 |
Height, open / weather protected (mm) | 1.425 / 1.950 | 1.475 / 2.170 | 1.625 / 2.170 | 1.695 / 2.170 | 1.725 / 2.170 | 1.780 / 2.150 |
Dry weight, open / weather protected (kg) | 1.000 / 1.400 | 1.300 / 1.800 | 1.400 / 1.900 | 1.600 / 2.100 | 1.700 / 2.250 | 2.600 / 3.070 |
Prime power – PRP (constant power supply with variable electrical loads over an unlimited time) constant according to the ISO standard. Can be used to supply variable electrical loads over an unlimited time. Ten per cent overload capacity for one hour within a 12-hour period.
Emergency power supply – LTP (Limited Time Running Power) (maximum power for a limited time) ISO standard rating blocked. Can be used for supplying variable electrical loads over a limited time. No overload capacity.
Control system
ComAp InteliNano / InteliLite / InteliGen